Wall-mounted gas boilers PROTHERM Jaguar, Cheetah, Panther, Lynx

Protherm skat error codes

The code Value Elimination
F.00 Temperature sensor error (NTC)
  • Check cable connections.
  • Replace temperature sensor (NTC).
  • Replace the cable harness.
  • Replace the electronic board.
F.10
F.13
F.19
F.20 Safety shutdown: safety temperature limiter
  • Switch on the boiler again.
  • Short-circuit the high limit safety cut-out.

If the boiler starts up again, replace the high limit safety cut-out.

  • Short-circuit the thermal fuse; if the boiler starts up again, replace the thermal fuse.
  • Replace the electronic board.
  • Replace the cable harness.
F.22 Dry start
  • Check the boiler for too low water pressure (<0.06 MPa (0.6 bar)).

    Check the tightness of all connections to the heating system.

  • Check the operation of the expansion tank.
  • Remove air from all radiators.
    Increase the heating system filling pressure.
F.41 Stuck Relay (HDO)
  • Switch the boiler off and on again.
  • Return the product settings to the factory settings (D.096).
F.55 Stuck contactor or relay
  • Disconnect the boiler.
  • Check all contactors and relays for defects and replace if necessary.
  • Call for service.
F.63 Communication failure with EEPROM - Return the product settings to the factory settings (D.096).
F.73 Water pressure sensor signal out of range (too low)
  • Check the wire to the water pressure sensor for breaks and short circuits.

Replace the faulty wire to the water pressure sensor.

  • Replace the water pressure sensor.
F.74
F.85 The water in the reservoir is frozen When the temperature at the NTC sensor falls below 3 ° C and there are no pressure surges, the boiler is automatically switched off.

When the temperature rises above 4 ° C, the boiler automatically switches on again.

F.86 Frozen external water heater If the temperature in the external storage tank falls below 3 ° C, the boiler will automatically shut down.

When the temperature rises above 4 ° C, the boiler automatically switches on again.

Indication

If the external water heater is not activated, the error is not displayed.

F.10 - Short circuit of the NTC sensor on the extract air

F.10 - Short circuit of the NTC sensor at the extract air

  • - a malfunction is indicated in the event of a short circuit of the NTC sensor installed on the OB terminal
  • - the message will be automatically deleted after reconnecting the NTC sensor
  • - a short circuit of the NTC sensor is detected if the voltage in its circuit is below 0.45 V
  • In this case, the sensor shows a deliberately incorrect value in comparison with the one indicated in the table.

RECOMMENDATIONS

  • Check sensor connection
  • Check sensor cables
  • Check sensor Resistance (replace if necessary)

F.10 - Short circuit of the NTC sensor at the extract air

F.13 - Short circuit of the NTC sensor of the external DHW storage tank

F.13 - Short circuit of the NTC sensor of the external DHW storage tank

- the malfunction is initiated on the boiler display in the event of a short circuit in the NTC sensor of the external DHW storage tank

- the message will be automatically deleted after reconnecting the NTC sensor

- a short circuit of the NTC sensor is detected if the voltage in its circuit is below 0.45 V

RECOMMENDATIONS

  • Check sensor connection
  • Check sensor cables
  • Check sensor Resistance (replace if necessary)
  • Proterm F.13 - Short circuit of the NTC sensor of the external DHW storage tank

Device

The design of the Protherm Cheetah 23 MTV boiler has a basic composition of assemblies and structural elements typical for most convective installations of this type.

The main units of the unit include:

  • Chromium-nickel alloy gas burner.
  • Primary copper heat exchanger.
  • Hydraulic group, which includes a three-way valve, water make-up and discharge devices, and other elements.
  • Secondary stainless steel heat exchanger.
  • Grundfos circulation pump.
  • Turbocharger fan.
  • Expansion tank with a capacity of 5 liters.
  • Electronic control board with microprocessor connected to an external display panel.
  • Self-monitoring sensor system, which continuously monitors the state of all boiler elements and signals about errors.

The boiler operates according to a typical scheme. The heat carrier enters the heat exchanger, where it is heated to the maximum temperature.

Then it is removed and enters the secondary heat exchanger, where hot water is heated. After that, the liquid enters the three-way valve, partially mixes with the return flow and acquires the set temperature corresponding to the set heating mode. The extract air then flows out to the external heating circuit.

Heating is provided by a gas burner, which automatically starts or stops when the set temperature limits of the coolant are reached.

The air supply for the organization of optimal combustion is provided by a fan, which simultaneously creates a draft for the removal of gas combustion products. Air intake is made from the external compartment of the coaxial chimney, purchased separately.

The operation of all units is monitored by a system of sensors that monitor the presence of a flame, gas or water pressure, signal all failures or malfunctions. The occurrence of any problems is immediately indicated on the display by an alphanumeric code indicating this or that error.

A complete list of codes is available in the user manual..

Download instruction

You can download the instruction Protherm Panther 23 MTV.

F.19 - Short circuit outside temperature sensor

F.19 - Short circuit outside temperature sensor

- malfunction is indicated in case of short circuit of the outside temperature sensor

- the message will be automatically deleted after reconnecting the NTC sensor

- a short circuit of the NTC sensor is detected if the voltage in its circuit falls below 0.45 V

- error is not indicated in case of inactive equithermal regulation function (E-)

- in this case, the boiler continues to work in normal heating mode (without equithermal regulation)

RECOMMENDATIONS

  • Check sensor connection
  • Check sensor cables
  • Check circuit voltage
  • Check sensor Resistance (replace if necessary)

F.19 - Short circuit outside temperature sensor

Error f20 on the Proterm Scat boiler

- malfunction is indicated in case of activation of the emergency thermostat as a result of boiler overheating

- the message will be automatically deleted after manually resetting the emergency thermostat

This emergency thermostat should also be installed in the copper pipe.

This thermostat is installed in older versions of the boiler, in boilers that come after 2012 this thermostat is not


there is a thermostat on the heat exchanger

- remove the protective rubber sheath from it

-in the middle you will see a small red button, press it and collect everything in reverse order. But find the cause of the overheating.

Not only press, but also identify the cause of overheating, why it happened. !!!

There is no circulation, check the pump and the air in the system. , there may be air in the heat exchanger, etc. To check the pump, unscrew the air bleed plug (you can see it visually or touch it with a screwdriver) The pump is Wilo. If it is broken and does not rotate, replace it. So that it would be more economical to buy one head, and not the entire pump assembly

Overheating just doesn't happen.

RECOMMENDATIONS

  • air in the boiler heat exchanger
  • Check the heating pump (no flow through the unit)
  • Check overheat thermostat

Types of boilers

There are two models of boilers Cheetah:

  • Atmospheric (with an open combustion chamber and natural smoke extraction).
  • Closed or turbocharged (a fan is used to supply air to the combustion chamber and forced removal of exhaust gases).

Models with an atmospheric burner are not recommended for installation in kitchens due to the possibility of a smoke smell due to external influences. For example, a strong wind or icing of a chimney can cause a decrease in draft, fraught with smoke in the room.

It is advisable to install atmospheric units in separate chambers with high-quality ventilation.

Turbocharged boilers are completely safe and can be installed in residential areas or in the kitchen.

They are guaranteed to remove exhaust gases, allowing you to keep the indoor air clean..

Both options have a full-fledged self-diagnosis system that constantly monitors the status of all nodes and immediately notifies about emergency situations.

F.22 - Loss of water - insufficient water pressure in the heating system

F.22 - Loss of water - insufficient water pressure in the heating system

- a malfunction is indicated if the water pressure in the heating system drops below 0.6 bar

- the message will be automatically deleted after the heating water pressure in the system rises above 0.6 bar

- as a result of adding water to the heating system

- an error message will not appear in the event of a pressure sensor malfunction

F.22 - Loss of water - insufficient water pressure in the heating system

The pressure sensor is used to determine the water pressure in the boiler (heating system). In the event of a lack of heating water in the boiler, the pressure sensor will transmit information to the boiler control board, which will give a command to stop it.

Operating principle

As the water pressure rises, the volume of the membrane carrying the magnet will increase. Opposite the magnet there is a Gall sensor, which changes the input voltage on the boiler control board, depending on the change in the parameters of the magnetic field. The change in the parameters of the magnetic field depends on the change in the distance of the Gall sensor in relation to the position of the magnet Measurement points

Proterm pressure sensor circuit F.22 - Water loss - insufficient water pressure in the heating system

Pressure sensor input voltage:

Measuring points 1 and 2 = 5 V DC Test values: Measuring points 1 and 3 At 1 bar / 1.7 V DC At 1.5 bar / 2 V DC At 2 bar / 2.3 V DC

RECOMMENDATIONS

  • Water pressure too low 0.3 bar. When filling the boiler with water, in this case it is not necessary to press the RESET button.
  • Faulty water pressure sensor. Replace.
  • Check for leaks in the boiler and heating system.
  • Check if the pump is working properly. It is possible that the pump may be blocked. disassemble it and check for proper operation and cleanliness.

PROTHERM Pantera. Double-circuit gas boilers with a PROTHERM Panther plate heat exchanger

Description

PROTHERM Panther boilers are designed for heating and heating hot water. Equipment: copper heat exchanger of the heating circuit, steel plate heat exchanger of the DHW circuit, modulating burner, expansion tank 5 l, circulation pump, safety group, the possibility of equithermal regulation. The boiler can be converted to liquefied gas. Models PROTHERM Panther 25 KTV and PROTHERM Panther 30 KTV are among the best selling wall mounted gas boilers

Specifications

A type25 KOV25 KTV30 KOV30 KTV35 KTV
Fuel, inlet pressurenatural gas, 13 mbar
power, kWt9.5 — 258.4 — 2510,5 — 28,89,4 — 29,911,2 — 35
Max. natural gas consumption, m3 / hour3,02,83,44,1
Combustion products removalchimneyturbochimneyturbo
Chimney diameter, mm13560 / 10013560 / 100
DHW productivity (dT = 25 deg C), lit / min1,5 — 12.01,5 — 14,41,5 — 16,8
Built-in expansion tank volume, l10,0
Boiler weight without coolant, kg3740344136
Gas connectionG 1/2 ″
Heating connection / water circuitsG 3/4 ″ / G 3/4 ″
Dimensions, H x W x D, mm800 x 440 x 338

F.41 - "Sticky" relay Proterm skat

F.41 - Stuck relay - this message will appear in case of 5 unsuccessful attempts of the boiler to unstuck the relay

  • - this message will appear in the case of a 5-fold unhurried attempt of the boiler to "unstuck" the relay

    In such cases, a LED will flash on the boiler control panel. The boiler will try to break the relay, and in case of failure, the display will show the error message F41. The boiler will run at minimum heat. After switching off and on again, the boiler will start working in operating mode, but the LED will continue to flash on the display. Contact a specialized service organization.

    error F.41 - Stuck relay

    - the message will disappear after the boiler is switched on and off again

    - the presence of a problem with the "sticky" relay after the boiler is switched on again continues to be signaled by the blinking of the HDO LED

    - the message will disappear after updating the boiler factory settings stored in the EEPROM memory (code d.96)

    - the error image is eliminated by switching off and again

    turning on the boiler

    - when switched on again, the boiler signals a sticking relay

    flashing HDO LED

    Verification:

    1. When the command to heat the heating water is canceled - at the end of the heating water cycle (opening the RT circuit) or hot water supply (the water temperature in the storage tank has reached the set value).
    2. When the "programmable temperature limiter" is activated, i.e. if the set temperature is exceeded by 5 ° C. Note: This function is activated when the boiler is in "standby" mode (ie there are no commands). The function starts when the detector is activated. If the boiler operates with a jumper and an external temperature sensor without heating the hot water supply, then a similar problem with the relay can be ignored until the temperature of the water in the system calculated by the equithermal regulation unit is exceeded by 5 ° C. Relay sticking test does not depend on the boiler operating mode. It is linked to the current state of the heating function. While the latter is disconnected, and the relay status is checked. The boiler is in a similar state whenever the heating elements stop working, i.e.: 1. after canceling the commands for heating the heating water and preparing the hot water supply, activating the anti-frost protection system - heating. 2. when activating the programmable temperature limiter - setpoint + 5 ° C Note: In case of a detector triggering (for example, in case of accidental closure of a relay contact), the function is activated (that is, similar to the one described in point 1). In addition, the function is activated in the following cases: DHW: cases 1 and 2 RH may occur: room thermostat - 1 and 2 RH: jumper + external temperature sensor

Introduction

Page 4

  • Picture
  • Text

4

You have become the owner of a direct-flow electric boiler for central heating systems with the ability to regulate thermal comfort. We hope that the Skat electric boiler will serve you for a long time and reliably. When installing and maintaining it, certain rules must be followed. Therefore, we ask you to carefully read the contents of this maintenance manual and, when working with the boiler, act in accordance with the recommendations and instructions given therein. We believe that the SKAT electric boiler will help you create a pleasant atmosphere and optimal thermal comfort at home. Please pay attention to the following main points:

1.

The boiler, together with the associated equipment, must be installed and used in accordance with the project documentation, the relevant laws and technical regulations in force, and the manufacturer's instructions.

2. The boiler must only be installed in

specially designed premises.

3. Putting the boiler into operation after

installations can only be carried out

a specialist from a specialized organization certified by Protherm.

4.

The boiler complies with the requirements of standards and regulatory documents in force on the territory of the Russian Federation, which is confirmed by a Certificate of Conformity issued by an authorized body, a Permit for use from the Federal Service for Environmental, Technological and Nuclear Supervision.

5.

In the event of any malfunctions, contact only a specialized service organization - non-professional

Introduction

tampering may affect the warranty of the equipment.

6.

The employee of the service organization putting the boiler into operation is obliged to familiarize the user with safety precautions when servicing equipment and controlling the operation of the boiler; operations that the user has the right to perform independently and operations that only a qualified specialist of the service organization has the right to carry out. If the specified service organization is also a supplier of the boiler, it is obliged to ensure that the original packaging of the boiler is kept in case of possible transportation.

7. Check the integrity and completeness.

delivery.

8. Make sure the type supplied to you is

the boiler according to its input parameters (indicated on the nameplate), is suitable for operation in this region. Input parameters mean: voltage of the electrical network.

9. In the case when you do not have a certain

to be sure of the correctness of your actions on boiler maintenance, find and carefully study the relevant instructions and recommendations contained in this maintenance manual, and act exclusively in accordance with them.

10.

Do not remove or damage the markings or inscriptions on the boiler.

Keep the original boiler packaging in case of possible transportation intact until the boiler is put into operation.

11.

Use only original spare parts for repairs. It is forbidden to interfere with the internal structure of the boiler and make any changes to its structure.

12.

In the event of a prolonged shutdown of the boiler, it is recommended to empty it and disconnect it from the power supply. This recommendation is made taking into account the general

Introduction

F.74 - Short circuit (signal - +5 V) of the extract air pressure sensor

F.74 - Short circuit (signal - 5 V) of the extract air pressure sensor

- this message will appear in the event of a short circuit (signal - +5 V) or an open circuit of the extract air pressure sensor

- the message will be automatically deleted after reconnecting the pressure sensor to the appropriate place

- a short circuit of the sensor with a +5 V signal is detected if the voltage rises above 4 V

RECOMMENDATIONS

  • Check sensor connector
  • Check the sensor
  • Press RESET of the boiler. If the error persists, replace the pressure sensor

F.74 - Short circuit (signal - 5 V) of the extract air pressure sensor

Rating
( 2 grades, average 5 of 5 )

Heaters

Ovens